Operation
6.10 Communication via SINAMICS Link
Enclosed Drives
390
Operating Instructions, 12/2018, A5E36652151A
Bus cycle and number of nodes
You can operate the bus cycle of the SINAMICS Link with the current controller cycle, either
synchronized or non-synchronized.
●
You set synchronized operation with p8812[0] = 1. A maximum of 64 nodes can then
communicate with one another via SINAMICS Link. To do so, set the maximum number
of nodes with p8811 (project selection):
Number of nodes/
project no.
Number of PZD
Bus cycle (µs)
64
16
1000 or 2000
16
16
500
12
24
500
8
32
500
●
A maximum of 64 participants can communicate with one another via SINAMICS Link.
If you change one of the parameters p8811, p8812, p8835 or p8836, then you must carry out
a POWER ON to accept the settings.
6.10.2
Topology
Only a line topology with the following structure is permitted for SINAMICS Link.
Figure 6-44 Maximum topology