Electrical installation
4.6 Power connections
Enclosed Drives
68
Operating Instructions, 12/2018, A5E36652151A
4.6.1
Cable lugs
Cable lugs
The cable connections on the devices are designed for cable lugs according to DIN 46234 or
DIN 46235.
For connection of alternative cable lugs, the maximum dimensions are listed in the table
below.
These cable lugs are not to exceed these dimensions, as mechanical fastening and
adherence to the voltage distances is not guaranteed otherwise.
Figure 4-3
Dimensions of the cable lugs
Table 4- 3
Dimensions of the cable lugs
Screw / bolts
Conductor cross-section
[AWG,MCM] ([mm²])
d2
[inch] ([mm])
b
[inch] ([mm])
l
[inch] ([mm])
c1
[inch] ([mm])
c2
[inch] ([mm])
M8
2/0 (70)
0.33 (8.4)
0.94 (24)
2.17 (55)
0.51 (13)
0.39 (10)
M10
350 (185)
0.41 (10.5)
1.46 (37)
3.23 (82)
0.59 (15)
0.47 (12)
M10
500 (240)
0.51 (13)
1.65 (42)
3.62 (92)
0.63 (16)
0.51 (13)
M12
4/0 (95)
0.51 (13)
1.10 (28)
2.56 (65)
0.63 (16)
0.51 (13)
M12
350 (185)
0.51 (13)
1.46 (37)
3.23 (82)
0.63 (16)
0.51 (13)
M12
500 (240)
0.51 (13)
1.65 (42)
3.62 (92)
0.63 (16)
0.51 (13)
M16
500 (240)
0.67 (17)
1.65 (42)
3.62 (92)
0.75 (19)
0.63 (16)