Operation
6.7 Communication according to PROFIdrive
Enclosed Drives
334
Operating Instructions, 12/2018, A5E36652151A
Error
value
Meaning
Comment
Additional
info
0x7A
Parameter %s [%s]: Write access
only in the commissioning state, data
record base configuration
(device: p0009 = 4).
–
–
0x7B
Parameter %s [%s]: Write access
only in the commissioning state,
device configuration
(device: p0009 = 1).
–
–
0x7C
Parameter %s [%s]: Write access
only in the commissioning state,
device download
(device: p0009 = 29).
–
–
0x7D
Parameter %s [%s]: Write access
only in the commissioning state,
device parameter reset
(device: p0009 = 30).
–
–
0x7E
Parameter %s [%s]: Write access
only in the commissioning state,
device ready (device: p0009 = 0).
–
–
0x7F
Parameter %s [%s]: Write access
only in the commissioning state,
device (device: p0009 not equal to 0).
–
–
0x81
Parameter %s [%s] must not be
written during download.
–
–
0x82
Transfer of master control is blocked
by BI: p0806.
–
–
0x83
Parameter %s [%s]: Requested BICO
interconnection not possible.
BICO output does not supply float values, however the
BICO input requires float values.
–
0x84
Parameter %s [%s]: Parameter
change inhibited
(refer to p0300, p0400, p0922)
–
–
0x85
Parameter %s [%s]: Access method
not defined.
–
–
0x87
Write job will not be executed.
The write job is rejected because know-how protection is
active.
–
0xC8
Below currently valid limit.
Modification request for a value that, although within
"absolute" limits, is below the currently valid lower limit.
–
0xC9
Above currently valid limit.
Modification request for a value that, although within
"absolute" limits, is above the currently valid upper limit
(e.g., specified by the actual converter rating).
–
0xCC
Write access not permitted.
Write access is not permitted because an access code is
not available.
–