Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without an encoder
Enclosed Drives
490
Operating Instructions, 12/2018, A5E36652151A
Table 7- 3
Optional motor data
Parameter
Description
Comment
p0320
Rated motor short-circuit current
For field weakening characteristic
p0322
Maximum motor speed
Maximum mechanical speed
p0323
Maximum motor current
De-magnetization protection
p0325
Rotor position identification current 1. Phase
-
p0327
Optional load angle
Optional otherwise leave at 90°
p0328
Reluctance torque constant
-
p0329
Rotor position identification current
-
p0341
Motor moment of inertia
For speed controller pre-control
p0344
Motor weight
-
p0350
Stator resistance, cold
-
p0356
Quadrature axis stator inductance Lq
-
p0357
In-line stator inductance Ld
-
Short-circuit protection
For short-circuits that can occur in the drive converter or in the motor cable, the rotating
machine would supply the short-circuit until it comes to a standstill. An output contactor can
be used for protection. This should be located as close as possible to the motor. This is
particularly necessary if the motor can still be driven by the load when a fault develops. The
contactor must be provided with a protective circuit against overvoltage on the motor side so
that the motor winding is not damaged as a result of the shutdown.
Control signal r0863.1 (VECTOR) controls the contactor via a free digital output; the
checkback contact of the contactor is connected to parameter p0864 via a free digital input.
This means that if the drive converter develops a fault with a shutdown response, at the
instant in time that the pulses are inhibited, the motor is isolated from the drive converter so
that energy is not fed back to the fault location.
Function diagrams
FP 4715
Actual speed value and pole position sensing, motor encoder (encoder1),
n_act_filter 5
FP 6721
Vector control - Id setpoint (PEM, p0300 = 2)
FP 6724
Vector control – Field weakening controller (PEM, p0300 = 2)
FP 6731
Vector control - Interface to Motor Module (PEM, p0300 = 2)