Operation
6.11 Communication via EtherNet/IP
Enclosed Drives
Operating Instructions, 12/2018, A5E36652151A
405
Identity Object, Instance Number: 1 hex
Supported services
Class
•
Get Attribute all
•
Get Attribute single
Instance
•
Get Attribute all
•
Get Attribute single
•
Reset
Table 6- 39 Class Attribute
No. Service
Type
Name
1
get
UINT16
Revision
2
get
UINT16
Max Instance
3
get
UINT16
Num of Instances
Table 6- 40 Instance Attribute
No. Service
Type Name
Value/explanation
1
get
UINT16 Vendor ID
1251
2
get
UINT16 Device Type
- Siemens Drive
0C hex
3
get
UINT16 Product code
r0964[1]
4
get
UINT16 Revision
5
get
UINT16 Status
See the following table
6
get
UINT32 Serial number
Bits 0 ... 19: Consecutive number;
Bits 20 … 23: Production identifier
Bits 24 … 27: Month of manufacture (0 = Jan,
B = Dec)
Bits 28 … 31: Year of manufacture (0 = 2002)
7
get
Short
String
Product name
Max. length 32 bytes
Table 6- 41 Explanation for No. 5 of the previous table
Byte Bit
Name
Description
1
0
Owned
0: Converter is not assigned to a controller
1: Converter is assigned to a controller
1
Reserved
2
Configured
0: EtherNet/IP basic settings
1: Modified EtherNet/IP settings
3
Reserved
4 … 7
Extended
Device Status
0: Self-test or status not known
1: Firmware update active
2: At least one I/O connection with error
3: No I/O connections
4: Incorrect configuration in the ROM
5: Fatal fault
6: At least one I/O connection is active
7: All I/O connections in the quiescent state
8 … 15: Reserved
2
8 … 11
Not used
12 … 15
Reserved