Electrical installation
4.9 Additional connections
Enclosed Drives
116
Operating Instructions, 12/2018, A5E36652151A
Note
Shutdown in the event of an overload
If these restrictions are not heeded, a fault trip may occur in the event of an overload (of the
infeed). To remedy this, adapt the current and/or torque limits in the Motor Module to match
the infeed.
Commissioning
For offline commissioning with STARTER, option L04 must be selected in the options list.
This ensures that a smaller infeed is selected during configuration.
Note
Consequences of not selecting option L04
Failing to select option L04 will produce inconsistencies and prevent downloading of the
project to the drive object.
No additional settings are required for commissioning via the AOP30 when Option L04 is
present.