Outputting Data and Controlling Operation through EtherNet/IP
294
FQ2 User’s Manual
●
Connection Settings
*1
If multi-cast connections are used, however, use an Ethernet switch that has multi-cast filtering, unless the tag set is received by all nodes
in the network.
*2
Set the same value as you set for the refreshing task period in the EtherNet/IP communications settings.
• If I/O memory addresses are specified for the communications areas, the information in the communications areas
will be cleared when the operating mode of the PLC changes unless addresses in the CIO Area, which are main-
tained, are specified.
• The following assembly object is required to specify instances when the EDS file is not used.
Assembly Object Settings
Parameter
Setting
Originator device (PLC)
Input tag set
PLC_tag_set_name-[**Byte]
**: This is the total size of the response area and
output area that you set.
Connection type
Any (default: multi-cast connection)
*1
Output tag set
PLC_tag_set_name-[20Byte]
Target device (Vision Sen-
sor)
Output tag set
Input_101-[**Byte]
**: This is the total size of the response area and
output area that you set.
Input tag set
Output_100-[20Byte]
Packet interval (RPI)
Any (default: 20.0)
*2
Parameter name
Setting
Remarks
Instance ID
100
Output connection
101
Input connection
Important
Summary of Contents for FQ2 Series
Page 1: ...User s Manual Smart Camera FQ2 Cat No Z326 E1 01A ...
Page 58: ...Setting Up Ethernet 56 FQ2 User s Manual MEMO ...
Page 90: ...Adjusting the Images That Were Taken 88 FQ2 User s Manual MEMO ...
Page 190: ...Adjusting Judgement Parameters during Operation 188 FQ2 User s Manual MEMO ...
Page 234: ...Functions Related to the System 232 FQ2 User s Manual MEMO ...
Page 404: ...Basic Troubleshooting 402 FQ2 User s Manual MEMO ...
Page 513: ...Index FQ2 User s Manual 511 Index 12 ...
Page 515: ......