238
Reading/Writing Function Block ITEMs
Appendix A
Blended PID (Block Model 013)
Note
Only optional tags can be set.
ITEM
type
ITEM
Tag ITEM
Data
description
Data
range
CX-Process Monitor screen (R:Read W:Write)
Over-
view
Screen
Control
Screens
Tuning
Screens
Trend
Screens
Batch
Trend
Screen
Segment
Program
2 Screen
(See
note.)
Graphic
Screens
Annun-
ciator
Screens
Alarm
Log
Screens
Contact
input
000
MT_ST
Stop block oper-
ation command
(0: Cancel stop,
1: Stop)
0 or 1
R
(Color)
R
(Color)
R
R
R
R
R
Analog
input
007
PV
PV input
0 to 9999
R
R
R
R
R
R
Parame-
ter
027
K1
Ratio
0 to 3.2000
R/W
R
R
R
R/W
Accumu-
lated
value out-
put
012
Q1
Accumulated
value
0 to 9999
R
R
R
R
R
013
Q2
Accumulated
value
0 to 9999
R
R
R
R
R
Analog
output
016
Y1
Instantaneous
value output
0 to 320.00%
R
R
R
R
R
R
029
Y2
Current Set Point
instantaneous
value output
0 to 320.00%
R
R
R
R
R
R
Parame-
ter
031
Cumulative devi-
ation High/high
alarm output
±
320.00%
R/W
R
R
R
R/W
032
Cumulative devi-
ation High alarm
setting
±
320.00%
R/W
R
R
R
R/W
033
Cumulative devi-
ation Low alarm
setting
±
320.00%
R/W
R
R
R
R/W
034
Cumulative devi-
ation Low/low
alarm setting
±
320.00%
R/W
R
R
R
R/W
Contact
output
036
DHH
Cumulative devi-
ation High/high
alarm output
0 or 1
R
(Color)
R
(Color)
R
(Color)
R
R
R
R
R
R
037
DH
Cumulative devi-
ation High alarm
output
0 or 1
R
(Color)
R
(Color)
R
(Color)
R
R
R
R
R
R
038
DL
Cumulative devi-
ation Low alarm
output
0 or 1
R
(Color)
R
(Color)
R
(Color)
R
R
R
R
R
R
039
DLL
Cumulative devi-
ation Low/low
alarm output
0 or 1
R
(Color)
R
(Color)
R
(Color)
R
R
R
R
R
R
Contact
input
017
ALM_OFF
Alarm stop
switch
0 or 1
R
(Color)
R
(Color)
R/W
R
R
R
R/W
014
S1
Counter reset
0 or 1
R/W
R
R
R
R/W
Parame-
ter
054
P
Proportional
band
0.1 to
999.9%
R/W
R
R
R
R/W
055
I
Integral time
0 to 9999 s
R/W
R
R
R
R/W
056
D
Differential time
0 to 9999 s
R/W
R
R
R
R/W
076
MH_LMT
High MV limit
±
320.00%
R/W
R
R
R
R/W
077
ML_ LMT
Low MV limit
±
320.00%
R/W
R
R
R
R/W
Contact
input
086
A/M_SW
Auto/Manual
switch
0 or 1
R/W
R/W
R
R
R
R/W
Parame-
ter
089
MV
Host display of
MV
±
320.00%
R/W
R/W
R
R
R
R/W
091
MV_ABN
MV error display
0: Normal, 1:
Error
0 or 1
R
R
R
R
R
R
098
MV_ IDX
MV index posi-
tion
–15.00 to
+115.00%
R
R/W
R
R
R
R/W
099
OP_MK
Label
0 to 15
R/W
R/W
R
R
R
R/W
Summary of Contents for CX-Process Monitor Plus 2
Page 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Page 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi Application Precautions 4...
Page 41: ...26 Basic Operating Procedure Section 1 2...
Page 243: ...228 Checking Configurations Section 5 7...
Page 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Page 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...