103
Batch Trend Screens
Section 4-10
• The trend data collection cycle and maximum save time in a Batch Trend
Screen are shown in the following table.
Note
1.
The collection cycle is set using the CRT Builder Dialog Box (Batch Trend
Screen) from the Builder Window. For details on collection cycle settings,
refer to
5-5-2 Overview of Screen Registration
.
2.
Depending on the number of combined function blocks and the model of
Loop Controller that is connected, it may not be possible to collect the data
within the collection cycle that is set.
If the data is displayed on a graph under these conditions, the data will be
updated with the same values as for the previous collection. To remedy this
situation, take measures such as lengthening the collection cycle interval.
Changing the Vertical Axis
Display
The display for the batch trend graph vertical axis can be changed for each
pen.
1,2,3...
1.
Click the Batch Trend Screen data display area.
2.
With the pen selected, click the vertical axis of the graph.
3.
The Vertical Axis Setting Dialog Box will be displayed. Set the vertical axis
display.
Note
If the scaling settings have been changed using the CX-Process Tool, change
the tag upper and lower limits in the Vertical Axis Setting Dialog Box to match
the new scaling values.
Item
Details
Collection cycle
(See note.)
1 s, 1 min
Maximum save time
4 hours (when collection cycle is 1 s)
10 days (when collection cycle is 1 min)
Click here.
Set the upper and lower limits.
Set the number of divisions.
Summary of Contents for CX-Process Monitor Plus 2
Page 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Page 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi Application Precautions 4...
Page 41: ...26 Basic Operating Procedure Section 1 2...
Page 243: ...228 Checking Configurations Section 5 7...
Page 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Page 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...