![background image](http://html1.mh-extra.com/html/omron/cx-process-monitor-plus-2/cx-process-monitor-plus-2_operation-manual_744195249.webp)
234
Reading/Writing Function Block ITEMs
Appendix A
Note
Only optional tags can be set.
Advanced PID (Block Model 012)
Parameter
054
P
Proportional band
0.1 to
999.9%
R/W
R
R
R
R/W
055
I
Integral time (0:
No integral action)
0 to
9999 s
R/W
R
R
R
R/W
056
D
Differential time
(0: No differential
action)
0 to
9999 s
R/W
R
R
R
R/W
076
MH_ LMT
High MV limit
±
320.00%
R
R/W
R
R
R
R/W
077
ML_ LMT
Low MV limit
±
320.00%
R
R/W
R
R
R
R/W
Contact
output
078
MHA
MV upper limit
output value
1: Upper limit or
more
0: Less than
upper limit
0 or 1
R
R
R
R
R
R
R
079
MLA
MV lower limit out-
put value
1: Lower limit or
less
0: Greater than
lower limit
0 or 1
R
R
R
R
R
R
R
Contact
input
086
A/M_ SW
Auto/Manual
switch
0: Manual, 1: Auto
0 or 1
R/W
R/W
R
R
R
R/W
R
Parameter
089
MV
Host display of
MV
±
320.00%
R/W
R/W
R
R
R
R/W
091
MV_ ABN
MV execution
error display
0: Normal, 1:
Error
0 or 1
R
R
R
R
R
R
098
MV_ IDX
MV execution
error display
0: Normal, 1:
Error
–15.00 to
+115.00%
R
R/W
R
R
R
R/W
099
OP_ MK
Label
0 to 15
R/W
R/W
R
R
R
R/W
ITEM
type
ITEM
Tag ITEM
Data
description
Data
range
CX-Process Monitor screen (R:Read W:Write)
Over-
view
Screen
Control
Screens
Tuning
Screens
Trend
Screens
Batch
Trend
Screen
Segment
Program
2 Screen
(See
note.)
Graphic
Screens
Annun-
ciator
Screens
Alarm
Log
Screens
Contact
input
000
MT_ST
Stop block opera-
tion command(0:
Cancel stop, 1:
Stop)
0 or 1
R
(Color)
R
(Color)
R/W
R
R
R
R
R
Analog
input
007
PV
PV input
–15.00 to
+115.00%
R
R
R
R
R
R
Parameter
008
HH_SP
High/high alarm
setting
–15.00 to
+115.00%
R
(– only)
R/W
R
R
R
R/W
009
H_SP
High alarm setting
–15.00 to
+115.00%
R
(– only)
R/W
R
R
R
R/W
010
L_SP
Low alarm setting
–15.00 to
+115.00%
R
(– only)
R/W
R
R
R
R/W
011
LL_ SP
Low/low alarm
setting
–15.00 to
+115.00%
R
(– only)
R/W
R
R
R
R/W
Contact
output
013
HH
High/high alarm
output
0 or 1
R
(Color)
R
R
R
R
R
R
R
R
014
H
High alarm output
0 or 1
R
(Color)
R
R
R
R
R
R
R
R
015
L
Low alarm output
0 or 1
R
(Color)
R
R
R
R
R
R
R
R
016
LL
Low/low alarm
output
0 or 1
R
(Color)
R
R
R
R
R
R
R
R
ITEM
type
ITEM
Tag ITEM
Data
description
Data
range
CX-Process Monitor screen (R:Read W:Write)
Over-
view
Screen
Control
Screens
Tuning
Screens
Trend
Screens
Batch
Trend
Screen
Segment
Program
2 Screen
(See
note.)
Graphic
Screens
Annun-
ciator
Screens
Alarm
Log
Screens
Summary of Contents for CX-Process Monitor Plus 2
Page 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Page 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi Application Precautions 4...
Page 41: ...26 Basic Operating Procedure Section 1 2...
Page 243: ...228 Checking Configurations Section 5 7...
Page 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Page 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...