131
System Monitor Screens
Section 4-17
!WARNING
Check the following items before starting to run the Loop Control Board:
• Do not allow the bank of the EM Area with the number specified for alloca-
tion to the HMI (human-machine interface) data to overlap with any other
area used by the CPU Unit or other Units. The block allocated for the HMI
is specified in ITEM 050 (EM Area Bank Allocated for HMI Memory = 0 to
12) of the System Common block. If areas overlap, the system may oper-
ate in an unexpected fashion, which may result in injury.
• Do not allow the area to which user link table data is written to overlap
with any other area used by the CPU Unit or other Units. If areas overlap,
the system may operate in an unexpected fashion, which may result in
injury.
• Analog Input/Output Units used in combination with the Loop Control
Board must be mounted correctly, and the unit number set on the front
panel of the Analog Input/Output Unit must match the unit number set on
the Field Terminal block. If the unit numbers do not match, input/output
(read/write) is performed on the data of another Special I/O Unit (whose
unit number is set on the Field Terminal block).
• The defaults of the System Common block on the Loop Control Board
must be set correctly.
!WARNING
Always stop the operation of the Loop Control Board before converting any of
the EM Area to file memory. If any part of the EM Area that is being used by
the Loop Control Board for the HMI is converted to file memory during Board
operation, the system may operate in an unexpected fashion, which may
result in injury.
Note
First sufficiently check system operation using the CX-Process Tool (check
the load rate, etc.: Execution, Operation, Monitor Run Status), and sufficiently
check operation (Monitor Run Status, Start) for the Function Block data that
has been created, and then change to actual operation. In particular, first
check that the load rate is 60% or less, and then change to actual operation.
1,2,3...
1.
Click the number button for the Loop Control Unit you want to use, as
shown.
The Run/Stop Command Dialog Box will be displayed as shown (for a Loop
Control Unit).
• Loop Control Unit is stopped.
Click here.
Summary of Contents for CX-Process Monitor Plus 2
Page 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Page 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi Application Precautions 4...
Page 41: ...26 Basic Operating Procedure Section 1 2...
Page 243: ...228 Checking Configurations Section 5 7...
Page 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Page 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...