![background image](http://html1.mh-extra.com/html/omron/cx-process-monitor-plus-2/cx-process-monitor-plus-2_operation-manual_744195149.webp)
134
System Monitor Screens
Section 4-17
4-17-4 Function Block Error Dialog Box Operations
1,2,3...
1.
Click the
E
Button.
The Function Block Error Dialog Box will be displayed.
Note
A Block database error indicates an error has occurred in the func-
tion block database.
The Function Block Error Dialog Box is displayed in green during normal
operation, and red if there is an error.
2.
Click the
Execution Error
or the
Block Database Error
button (Battery
Error is displayed only and cannot be selected).
The Details of Function Block Error Dialog Box will be displayed.
Block Database Error
0 = Normal (no errors), –1 = Block number not in use, 90 = Relevant Function
Block has a database error.
Execution Error
0 = Normal (no errors), –1 = Block number not in use, other numbers (1 to 89)
= Error code.
The following table gives the function error codes.