69
Example Function Blocks for Data Exchange
Section 3-2
Actual Setting Procedure
The following settings are used to set a bit’s status from Monitor Plus.
1,2,3...
1.
Set the tag for Monitor Plus in the Internal Switch (Block Model 209) block’s
S1 ITEM. Set the tag type to
Set
.
2.
Set the Contact Distributor block’s S1_AD ITEM (S1 source designation)
to the Internal Switch block’s S1 ITEM. In this case, S1_AD is set to
103011.
3.
Set the Contact Distributor block’s E1_AD ITEM (E1 destination) to the Ba-
sic PID block’s R/L_SW ITEM (Remote/Local switch). In this case, E1_AD
is set to 001026.
Monitor Plus
Loop Control Unit or Board
Internal
Switch
(Block
Model 209)
Set tags for Monitor Plus.
(Select
Setting
to write data.)
Function
block
Function
block
Specify the tags
for Monitor Plus
and write data.
CPU Unit
Contact
Distributor
(Block
Model 201)
I/O memory
Contact
Contact
Contact
Contact
Write
Select
Setting.
Summary of Contents for CX-Process Monitor Plus 2
Page 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Page 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi Application Precautions 4...
Page 41: ...26 Basic Operating Procedure Section 1 2...
Page 243: ...228 Checking Configurations Section 5 7...
Page 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Page 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...