Troubleshooting
Section 6
An illegal response was received from
the Net
@
, Node
@
PLC.
An illegal response was received from
the CPU Unit.
Check to make sure that the FinsGate-
way settings are correct.
Check for an error at the CPU Unit and
remove the cause of the error if neces-
sary.
A timeout occurred in communica-
tions with an LCB registered at Net
@
,
Node
@
.
A timeout occurred in communica-
tions with an LCU registered at Net
@
,
Node
@
, Unit
@
.
A timeout occurred in communications
with the Loop Controller.
Check to make sure that the Loop Con-
troller is correctly installed.
An illegal response was received from
an LCB registered at Net
@
, Node
@
.
An illegal response was received from
an LCU registered at Net
@
, Node
@
,
Unit
@
.
An illegal response was received from
the Loop Controller.
Check to make sure that the Loop Con-
troller is correctly installed.
Check for an error at the Loop Control-
ler.
The LCB model registered at the
Net
@
, Node
@
is incorrect.
The LCU model registered at Net
@
,
Node
@
, Unit
@
is incorrect.
The Loop Controller model is incorrect.
The registered Loop Controller is not
the one that is connected. Check the
model.
The EM bank number for the LCB
registered at Net
@
, Node
@
is incor-
rect.
The EM bank number used by the LCB
is incorrectly set.
The EM bank numbers that can be used
by Loop Control Boards are 0 to C. Set
a number within this range.
The HMI interface setting for the LCB
registered at Net
@
, Node
@
is incor-
rect.
The HMI interface settings for the LCB
are not enabled.
The CX-Process Monitor Plus will not
operate correctly if the HMI interface
settings for the LCB are not enabled.
Enable the HMI interface settings.
Block Execution Error is displayed in
the System Monitor Messages.
An execution error has occurred in the
Function Block data downloaded to the
Loop Control Unit.
1. Click the
E
Button on the Loop Con-
trol Unit in the System Monitor
Screen.
2. Click the
Execution Error
Button in
the Function Block Error Dialog Box.
3. Check the Execution error’s Function
Block using the Details Of Function
Block Error Dialog Box.
4. Correct the settings for the relevant
Function Block using CX-Process
Tool.
Unit Address Setting Disagrees With
Actual Unit Number is displayed in
the System Monitor Messages.
The actual Loop Control Unit’s address
and the node PLC’s Unit address in the
System Monitor Builder Screen do not
agree.
Make sure the actual Loop Control
Unit’s address and the System Monitor
Builder’s node PLC Unit’s address
agree.
ERROR CODE: is displayed during
Loop Control Unit Run/stop in the
System Monitor Screen.
The FinsGateway setting or the network
setting is incorrect.
Correct the FinsGateway setting and
the network settings.
An address error message is dis-
played on the System Monitor
Screen.
It’s possible that the ladder program or
another Unit is writing data to the area
of memory used for system information.
The system information is stored in the
following areas.
DM 16020 to DM 16044 for the Loop
Control Unit
20 words from the first word used for the
HMI for the Loop Control Board
Check the ladder program and Unit con-
figuration to see if the system informa-
tion area is being written to.
Phenomenon
Cause
Action
Summary of Contents for CX-Process Monitor Plus 2
Page 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Page 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi Application Precautions 4...
Page 41: ...26 Basic Operating Procedure Section 1 2...
Page 243: ...228 Checking Configurations Section 5 7...
Page 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Page 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...