144
System Monitor Settings
Section 5-3
Setup Dialog Box
Refer to the following sections for details on the functions of each button.
5-3
System Monitor Settings
Using the System Monitor Setting Window, register the PLC and Loop Control
Unit/Board to be monitored using the System Monitor Screen. Also register
the local computer to perform the monitoring.
The setting items are as follows:
When the monitor process is started with serial (Host Link) communications
by clicking the
Run
Button in the Main Window or the Setup Dialog Box, Fins-
Gateway communications will start according to the settings of the following
communications conditions.
• Communications type: Serial (Host Link)
• COM port used and baud rate
Note
The PLC settings (node address, Unit address, etc.) set here can
be used only from the System Monitor Screen. Actual communica-
tions processing depends on the network address, node address,
and Unit address set using the CX-Process Tool. Controller Link
and Ethernet settings within the computer settings made here can
also be used only from the System Monitor Screen. Perform actual
communications processing by manually starting FinsGateway.
3. Configures the screen.
Refer to
5-5 Screen
Configuration
for details.
2. Opens the Graphic Screen Create
Window.
Refer to
5-4 Creating Graphic Screens
.
1. Sets the System
Monitor Screen. Refer
to
5-3 System Monitor
Settings
for details.
Sets auto-start, tuning trend scale
display, multi-screen, label
information, alarm sound
information, and ten-key. Refer to
5-6 System Information Settings
for details.
PLC setting
PLC node number (address)
Use the System
Monitor Screen for
this setting.
Unit address of the Loop Control Unit/
Board (The unit address of the Loop Con-
trol Board is always 225.)
Computer setting Computer node number (default is 32)
Communications type (CLK, Serial, Ethernet) (Use the System
Monitor Screen to set CLK or Ethernet communications.)
For serial connections, you must also set the COM port and baud
rate.
Summary of Contents for CX-Process Monitor Plus 2
Page 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Page 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi Application Precautions 4...
Page 41: ...26 Basic Operating Procedure Section 1 2...
Page 243: ...228 Checking Configurations Section 5 7...
Page 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Page 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...