235
Reading/Writing Function Block ITEMs
Appendix A
Note
Only optional tags can be set.
Contact
input
017
ALM_OFF
Alarm stop switch
0: Alarm, 1: Stop
0 or 1
R
(Color)
R/W
R
R
R
R/W
R
Parameter
019
PV_ ABN
PV execution
error display
0:Normal,
1:Error
→
MAN-
UAL mode
0 or 1
R
R
R
R
R
R
R
023
SP
Local Set Point
setting
–15.00 to
+115.00%
W
W
W
024
CAS_SET
Set Point setting
mode (default)0:
Local only1:
Remote/Local
Note: Setting to 0
invalidates
ITEM026.
0 or 1
R
R
R
R
R
R
026
R/L_SW
Remote/Local
switch
0: Local, 1:
Remote
Note: Valid only
when ITEM024 is
1
0 or 1
R/W
R/W
R/W
R
Analog
output
029
SP
Current Set Point
output
–15.00 to
+115.00%
R
R
R
R
R
R
Parameter
035
AT
AT command/AT
Executing
0.1
R/W
R
R
R
R/W
R
R
041
DVA_SP
Deviation alarm
setting (Hystere-
sis is set at
ITEM012.)
0 to
115.00%
R/W
R
R
R
R/W
Contact
output
042
DVA
Deviation alarm
output
0 or 1
R
R
R
R
R
R
R
R
R
Parameter
054
P
Proportional band
0.1 to
999.9%
R/W
R
R
R
R/W
055
I
Integral time (0:
No integral action)
0 to
9999 s
R/W
R
R
R
R/W
056
D
Differential time
(0: No differential
action)
0 to
9999 s
R/W
R
R
R
R/W
076
MH_LMT
High MV limit
±
320.00%
R
R/W
R
R
R
R/W
077
ML_ LMT
Low MV limit
±
320.00%
R
R/W
R
R
R
R/W
Contact
output
078
MHA
High MV limit
arrival output
1: Limit or more,
0: Less than limit
0 or 1
R
R
R
R
R
R
R
Contact
output
079
MLA
Low MV limit
arrival output
1: Limit or less,
0: Not limit or less
0 or 1
R
R
R
R
R
R
R
Contact
input/
parameter
086
A/M_SW
Auto/Manual
switch
0: Manual, 1: Auto
0 or 1
R/W
R/W
R
R
R
R/W
R
Parameter
089
MV
Host display of
MV
±
320.00%
R/W
R/W
R
R
R
R/W
091
MV_ABN
MV execution
error display
0: Normal, 1:
Error
0 or 1
R
R
R
R
R
R
R
R
098
MV_ IDX
MV index position
–15.00 to
+115.00%
R
R/W
R
R
R
R/W
099
OP_MK
Label
0 to 15
R/W
R/W
R
R
R
R/W
ITEM
type
ITEM
Tag ITEM
Data
description
Data
range
CX-Process Monitor screen (R:Read W:Write)
Over-
view
Screen
Control
Screens
Tuning
Screens
Trend
Screens
Batch
Trend
Screen
Segment
Program
2 Screen
(See
note.)
Graphic
Screens
Annun-
ciator
Screens
Alarm
Log
Screens
Summary of Contents for CX-Process Monitor Plus 2
Page 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Page 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi Application Precautions 4...
Page 41: ...26 Basic Operating Procedure Section 1 2...
Page 243: ...228 Checking Configurations Section 5 7...
Page 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Page 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...