93
Tuning Screens
Section 4-8
Note
Execution of AT can be cancelled from the above dialog box by inputting 0 in
the New Data Field and clicking the
OK
Button. (The value for AT displayed in
the upper-left region of the Tuning Screen will return to 0.)
Changing P, I, D
The following example shows how to change P (the proportional band).
1,2,3...
1.
Click
Proportional Band (P)
displayed in the upper center of the screen.
The Change Data Dialog Box will be displayed.
2.
Select the Change To Field.
The ten-key dialog box will be displayed as shown.
Note
Refer to
5-6 Labels, Alarm Sounds, and Ten-key Settings
for set-
tings to disable the ten-key pad (i.e., to input directly from the key-
board).
3.
After using the mouse (or the keyboard) to enter a numerical value, click
the
OK
Button.
The display will return to the Change Data Dialog Box shown in Step 1.
4.
Click the
OK
Button.
You can change the settings for I (integral time) and D (differential time) in the
same way.
Changing Other Settings
You can use the procedure explained above to change the settings for MV
High/Low Limit, High/High Alarm, High Alarm, Low/Low Alarm, Low Alarm,
and Deviation Alarm in the same way.
Executing Fine Tuning
Fine tuning (FT) can be executed for either Basic PID (011) or Advanced PID
(012). Fine tuning lets the user use fuzzy inferences to set PID constants as
required for more accurate control.
Summary of Contents for CX-Process Monitor Plus 2
Page 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Page 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi Application Precautions 4...
Page 41: ...26 Basic Operating Procedure Section 1 2...
Page 243: ...228 Checking Configurations Section 5 7...
Page 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Page 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...