![background image](http://html1.mh-extra.com/html/omron/cx-process-monitor-plus-2/cx-process-monitor-plus-2_operation-manual_744195018.webp)
3
CX-Process Monitor Plus
Section 1-1
CX-Process Monitor Plus Functions
Note
Only the following data can be monitored and set with the CX-Process Moni-
tor Plus and tag names must be set to enable monitoring and setting. Use CX-
Process Tool Ver. 3.2 or higher to set the tag names.
---
Screen
Monitoring operating
status
Controlling operation
Monitoring alarm status
User-defined
screens
Overview
---
---
OK
Control
OK (Display PV bar)
OK (Change SP, switch
between auto/manual,
and perform manual oper-
ations)
OK
Tuning
OK (Display PV, SP, and
MV trends for 1 loop)
OK (Change SP, and
change P, I, D, etc.)
OK (Change bar graph
colors)
Trend
OK (Display Control Block
or analog signal trends)
---
OK
Batch Trend
OK (Display Control Block
or analog signal trends)
---
---
Segment
Program 2
OK (Display Segment
Program 2 trends)
OK (Run/stop operation
at the relevant Segment
Program 2 Block)
OK (Errors related to the
relevant Segment Pro-
gram 2 Block)
Graphic
OK (Display status for
contact or analog signal
graphics)
OK (Turn ON/OFF the
contact, and set the ana-
log value)
OK
Annunciator
---
---
OK (Use colors or sound
to notify of an alarm)
Operation Guide OK (Display message
when Internal Switch is
turned ON)
---
OK
System Monitor
OK (Display the run/stop
status for the Loop Con-
trol Unit/Board, display
Execution errors, RAM
checksum errors, and
battery errors, and moni-
tor the status of the CPU
Unit control mode, etc.)
OK (Run/stop command
for the Loop Control Unit/
Board)
OK
System screens
Alarm Log
---
---
OK (Stored when an
alarm occurs)
Operation Log
---
OK (Stores run operation
history, e.g., SP change,
etc.)
OK
System Monitor
Log
OK (Displays run/stop
command history and
Execution error history
when an error occurs)
---
OK
Summary of Contents for CX-Process Monitor Plus 2
Page 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Page 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi Application Precautions 4...
Page 41: ...26 Basic Operating Procedure Section 1 2...
Page 243: ...228 Checking Configurations Section 5 7...
Page 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Page 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...