![background image](http://html1.mh-extra.com/html/omron/cx-process-monitor-plus-2/cx-process-monitor-plus-2_operation-manual_744195097.webp)
82
Control Screens
Section 4-7
Screen Selection Buttons
4-7
Control Screens
4-7-1
Outline
Use Control Screens to monitor and set the Control Block and part of the
Operation Block, to monitor analog signals, and to monitor and set contact
signals. For the Control Block in particular, use the Control screen to perform
such operations as monitoring Set Point (SP), Process Variable (PV), Manipu-
lated Variable (MV) run status, and Set Point (SP) changes, etc.
Click the
Control Screen
Button in the Overview screen to display the follow-
ing information on the Control Screen.
• You can display up to a maximum of eight loops per screen of PID, Indica-
tors, and other Control Blocks as on-site Instrument images. The maxi-
mum is 400 screens x eight loops.
• You can perform SP changes, auto/manual switching, and manual opera-
tions, etc. (Items indicated by a Button can be changed. Items without a
Button are displayed only.)
• You can also move to the Tuning Screen.
Button name
Function
Overview
Displays the Overview Screen. If multiple Overview Screens
are registered, a pull-down menu will be displayed from which
you can select the Overview Screen you want.
Alarm
Displays the Alarm Log Screen.
Operation Log
Displays the Operation Log Screen.
Operation Guide
Displays the Operation Guide Screen.
System Monitor
Displays the System Monitor Screen to show system status.
System Monitor Log Displays the System Monitor Log Screen, which registers sys-
tem messages.
About
Displays information on the CX-Process Monitor Plus version.
External applica-
tion start buttons
Start external applications set in the System Info.
Block name (mode)
Send source function block, or ITEM
Target function block
Control Blocks: Basic PID (011), Advanced PID (012), Blended PID (Block Model 013), Batch
Flowrate Capture (Block Model 014), Indication and Setting (031), Indication and Operation
(032), Ratio Setting (033), Indicator (034), 2-position ON/OFF (001), 3-position ON/OFF (002)
Operation Blocks: High/Low Alarm (111), Segment Program 2 (157), ON/OFF Valve Manipula-
tor (221), Motor Manipulator (222), Reversible Motor Manipulator (223), Motor Opening Manip-
ulator (224), Timer (205), Counter (208)
The following for all function blocks:
Analog input signals (Input Selector (Block Model 162))
Analog output signals (Constant Generator (Block Model 166))
Contact input signals or contact output signals for all function blocks, or contact value parame-
ters (Contact Distributor (Block Model 201) + Internal Switch (Block Model 209))
Display
SP, PV, MV, A/M status, R/L status (See note 1), bar color change analog signal when an alarm
occurs, contact signal
Setting
SP, MV (only in manual mode), A/M switching (See note 3), R/L switching (See notes 1 and 2.)
Contact signal (See note 4.)
Summary of Contents for CX-Process Monitor Plus 2
Page 1: ...CX Process Monitor Plus Ver 2 Cat No W428 E1 02 SYSMAC WS02 LCMC1 EV2 OPERATION MANUAL...
Page 2: ...WS02 LCMC1 EV2 CX Process Monitor Plus Ver 2 Operation Manual Revised January 2007...
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x...
Page 15: ...xvi Application Precautions 4...
Page 41: ...26 Basic Operating Procedure Section 1 2...
Page 243: ...228 Checking Configurations Section 5 7...
Page 267: ...252 Reading Writing Function Block ITEMs Appendix A...
Page 269: ...254 Differences between Trend Screens and Batch Trend Screens Appendix B...