Operator Qualifications and Primary Responsibilities
• Testing with
CPC 100
should only be carried out by authorized and qualified
personnel. Clearly establish the responsibilities!
• Personnel receiving training, instruction, direction, or education on
CPC 100
should remain under the constant supervision of an experienced operator
while working with the equipment.
Safe Operation
When setting
CPC 100
into operation, follow the instructions in ”Putting
CPC 100 into Operation” on page 2-46.
If you have a cardiac pacemaker, do not use
CPC 100
! Before operating
CPC 100
, make sure there is no person with a cardiac pacemaker in the
immediate vicinity.
Never use
CPC 100
without a solid connection to ground with at least 6mm².
Use a ground point as close as possible to the test object.
Power Supply
• Supply
CPC 100
only from a power outlet that has protective earth (PE).
• An error message (313) appears if either the PE connection is defective or
the power supply has no galvanic connection to ground. In this case, make
sure that the PE connection is intact. If the PE connection is intact and the
error message still appears, select the "Disable ground check" check box at
the
Device Setup
tab in the
Options
view (see ”Device Setup” on page
• Ground the isolating transformer outputs on the N (neutral) output or select
the "Disable ground check" check box as described above.
• Instead of supplying
CPC 100
from phase - neutral (L1-N, A-N), it may also
be supplied from phase - phase (for example, L1-L2; A-B). However, the
voltage must not exceed 240V AC.
• Fuse-protect the power supply (16 A automatic circuit-breaker).
• Do not use an extension cable on a cable reel to prevent an overheating of
the cord; run out the extension cord.
• Keep extension cables as short as possible to prevent power loss.
DANGER!
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...