CPC 100 V1.41
7 - 24
Measurements
Once all settings are defined, press the I/O (test start/stop) push-button to start
the test.
The test voltage increases in a ramp characteristic from 0V to Vtest. Vtest is
then applied to the output for the specified time span. The measurements are
continuously taken. Afterwards Vtest decreases in a ramp characteristic.
When the measurements are taken, finish the test by assessing it.
To learn more about test assessment, refer to ”Test Assessment” on page 10-2.
VAC:
injected voltage from
2kV AC
output at the time the test turned
off
IAC:
measured current between the transformer’s primary and
secondary windings at the time the test turned off
Imax:
maximum measured current between primary and secondary
winding during the entire test cycle