![Omicron CPC 100 Reference Manual Download Page 340](http://html2.mh-extra.com/html/omicron/cpc-100/cpc-100_reference-manual_3988877340.webp)
CPC 100 V1.41
16 - 24
Insulation
N (black socket) is connected to N of the
V2AC
input
Apart from this, the input is insulated against all other
inputs and outputs. Voltage with reference to earth
must not exceed 300V
rms
and 420V
peak
on either input
socket.
Reinforced insulation against mains power supply, all
interfaces and other safety low-voltage circuits.
Maximum voltage
330V
rms
/ 470V
peak
Accuracy
300V:
typ. error < ± 0.05% (rd) ± 0.05% (fs),
guaranteed < ± 0.1% (rd) ± 0.1% (fs)
30V:
typ. error < ± 0.05% (rd) ± 0.05% (fs),
guaranteed < ± 0.1% (rd) ± 0.1% (fs)
3V:
typ. error < ± 0.1% (rd) ± 0.05% (fs),
guaranteed < ± 0.2% (rd) ± 0.1% (fs)
300mV: typ. error < ± 0.15% (rd) ± 0.05% (fs),
guaranteed < ± 0.3% (rd) ± 0.1% (fs)
Possible crest factor: < 1.5
Phase tolerance at full scale of all ranges:
typ. error < ± 0.1°
guaranteed < ± 0.2°
Input resistance
500k
Ω
Resolution
Measurement
Display
300V:
15 mV/bit
30V:
1.5 mV/bit
3V:
150
μ
V/bit
0.3V:
15
μ
V/bit
5
μ
V
300V V1AC input
N
N
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...