CPC 100 V1.41
16 - 4
Power Supply
Important
: for safety-relevant issues regarding
CPC 100
power supply, also
refer to ”Power Supply” on page 1-6.
Table 1:
Main power supply
technical data
Main Power Supply
Connection
AC voltage, 1 phase, connector IEC320/C20
Voltage single phase
– nominal voltage
– permitted range
100 ... 240V AC
85 ... 264V AC
Power fuse
Automatic circuit breaker with magnetic overcurrent
tripping at I > 16A
Power consumption
< 3500VA
< 7000VA short-term (< 10s)
Frequency
– nominal
frequency
– permitted range
50 / 60Hz
45 ... 65Hz
Note:
If the power supply is
≤
190V AC,
CPC 100
cannot provide the full
output power at the
800A AC
output. The same applies when an
external booster is used. Therefore, in order to gain the full output
power, provide a sufficient power supply (190V ... 240V AC).