CPC 100 V1.41
3 - 2
Quick starts in "measuring" state with de-activated outputs, displaying the
measured values in the measurement table of the Quick test card.
The measurements as well as the indication of the binary input’s signal status
(refer to ”Bin.In:” on page 12 of this chapter) are updated with an interval of
approx. 0.5s.
After having set all necessary parameters (more about this in the following
sections), press the I/O (test start/stop) push-button. The Quick test card enters
the "on" state, the set power output value is switched to the
CPC 100
outputs,
the measuring continues.
Pressing the Quick test card menu key K
E E P
R
E S U L T S
saves the currently
measured values and "freezes" their display in the measurement table. Both the
"measuring" and the "on" state remain active, the measurement continues in a
new line of the measurement table.
While in "on" state, pressing the I/O (test start/stop) push-button terminates the
test. The
CPC 100
outputs are turned off, and Quick returns to the "measuring"
mode.
Pressing the S
E T T I N G S
menu key opens the
Settings
page. The
Settings
page allows setting the test cards individually. As a rule, do not use the
Settings
page but the
Device Setup
tab in the
Options
view (see ”Device Setup” on
page 2-33) to set the test cards. For more information, see ”Settings Page” on
page 2-28.
Note 1:
When testing capacitive test objects using voltages
≥
500V, make
sure that the test object’s capacity does not exceed 25nF.
Together with the test object’s capacity, the leakage inductance of
CPC 100
internal output transformer forms a series resonant circuit.
Especially at frequencies
>
50/60Hz this may result in voltage
superelevation.
Note 2:
Never use
Quick
to measure the resistance of windings with a high
inductance because turning off the DC source results in life-
threatening voltage levels.
For this kind of measurement only use the special winding resistance
test card
RWinding
!
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...