CPC 100 V1.41
4 - 12
Test settings
Figure 8:
CTBurden
test card
with test results
Navigate to the parameter fields, and enter the values according to your test
requirements:
Selecting the check box "Manual input" lets you enter the value for Vsec
manually, for example, when Vsec was measured with an external volt meter
rather than at input
V1AC
.
Measurements
Isec:
nominal secondary current
Itest:
secondary injection current from
6A AC
output
f:
output frequency
Auto
select check box for automatic test (default), clear for manual
test (refer to page 4-13).
Isec:
actual secondary current, measured via input
IAC
Vsec:
secondary voltage at the burden, measured at input
V1AC
,
and phase angle
ϕ
relative to Isec
Burden:
burden in VA: Isec nom × (Vsec act × Isec nom/Isec act)
cos
ϕ
cosine of phase angle
ϕ