Current Transformer
4 - 23
Measurements
Note:
The VDC voltage is limited to 10 V. If n/a appears in the VDC box,
decrease the test current to lower the voltage generated at the transformer’s
secondary winding below 10 V.
IDC:
actual test current from
6A DC
output or
400A DC
output
VDC:
voltage that IDC generates at the transformer’s secondary
winding, measured at
V DC
input
R meas:
transformer’s winding resistance, calculated from VDC / IDC
Time:
total elapsed test time
Dev:
deviation in % between the maximum and the minimum
measured values evaluated within the last 10 seconds of the
measurement. The results are considered stable if Dev < 0.1%.