CPC 100 V1.41
6 - 14
It is recommended to perform all winding resistance measurements with the
CP SA1
connected to the
CPC 100
V DC
input sockets to protect yourself and
CPC 100
from high-voltage hazards. The
CP SA1
must be used for
measurements using
400A DC
output. Before using
CP SA1
, you can check its
functionality by following the test procedure in ”CP SA1” on page 17-14. If the
CP SA1
is defective, contact OMICRON electronics sales office (for ordering
information, see ”Ordering Information for CP SA1” on page 17-14). Before
disconnecting the test leads, short-circuit the transformer’s terminals and then
remove the wirings to
CPC 100
.
Figure 9:
Winding resistance test
using
400A DC
output
Due to the significant time span needed for the transformer’s inductance to finish
its loading process, this test evaluates the deviation of measured values within
a time interval of 10 seconds. The winding resistance is continually measured
and stored in
CPC 100
internal memory. The calculated difference between the
maximum and minimum measured values in % within the last 10 seconds is
displayed.
Furthermore, this test comprises the option to take a temperature compensation
for copper (Cu) into consideration (refer to page 6-17).
CP SA1
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...