Voltage Transformer
5 - 17
If
CPOL
detects the same signal characteristic at a test point, it considers the
polarity as OK, and lights up the green LED.
If the signal characteristic is inverted or distorted,
CPOL
considers the polarity
not OK, and lights up the red LED.
If
CPOL
detects a signal that is too low, both LEDs light up at the same time.
Remedy: increase the signal magnitude.
If you are not quite certain whether your measurement is correct, you can
confirm it by reversing the probes of
CPOL
. In that case, the other LED should
light up.
The battery of CPOL
If the capacity of
CPOL
’s battery gets low, both LEDs start flashing
simultaneously. As long as the LEDs are flashing,
CPOL
’s battery provides
sufficient power to continue working. However, the battery should be changed
as soon as possible.
Never operate
CPOL
with an open battery compartment. A life-hazardous
voltage level may occur in the battery compartment if
CPOL’s
probe touches a
test point with high-voltage potential!
Note:
If you detect a wrong polarity in the current path, turn off
CPC 100
first,
and only then disconnect the terminals.
☺
☺
+
☺
+
on/off
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...