Preface
1 - 13
Designated Use
CPC 100
, in conjunction with its accessories or as a stand-alone unit, is a multi-
purpose primary test set for commissioning and maintaining substation
equipment. It performs current transformer (CT), voltage transformer (VT) and
power transformer (TR) tests. Furthermore it is used for contact and winding
resistance testing, polarity checks as well as primary and secondary protection
relay testing.
The various, partly automated tests are defined and parameterized via the front
panel control of a built-in ePC (
⇒
Glossary).
Functionality of
CPC 100
• Current transformer (CT)
– testing ratio, polarity (and burden) with injection to current input
– testing ratio, polarity (and burden) with a current clamp
– testing secondary burden
– measuring the excitation curve
– measuring winding resistance
– dielectric withstand voltage test (2kV AC)
– polarity check
– testing ratio and polarity by measuring the voltage ratio
– testing ratio and polarity of a Rogowski coil
– testing ratio and polarity of low power current transformer
• Voltage transformer (VT)
– testing ratio and polarity
– testing secondary burden
– dielectric withstand voltage test (2kV AC)
– polarity check
– testing ratio & polarity of non-conventional electronic voltage transformers
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...