Voltage Transformer
5 - 23
Measurements
Selecting the check box "Manual input" lets you enter the value for Vsec
manually, for example, when Vsec was measured with an external volt meter
rather than at input
V1AC
.
Vprim:
actual output voltage at
2kV AC
output
that is injected into the
electronic voltage transformer’s primary side
Vsec:
secondary voltage measured at
V2AC,
and its phase angle
relative to Vprim nominal
Ratio:
ratio Vprim /Vsec., here 10000.0/
√
3:1.002
/√
3
1
1. The value 1.002/
√
3 is calculated as follows:
Vsec act x (Vprim nom / Vprim act) = 200.4mV x (10000V/
√
3 / 2kV) = 1.002 V/
√
3
and deviation of voltage ratio in %.
((Kn x Vsec - Vprim) / Vprim) x 100%
2
((10000V / 1V x 0.2004V - 2000V) / 2000V) x 100% = 0.205%
2. Kn = rated transformation value, here: 10000V / 1V
Polarity:
displays the status of the polarity
OK
= phaseVsec - phaseVprim = -45° < 0° < 45°
NOT OK = all other cases