Introduction
2 - 3
High-Voltage and High-Current Outputs
When
CPC 100
outputs high current, observe the allowed duty cycles that may
apply to the selected AC output range.
For more information please refer to
”CPC 100 Outputs” on page 16-5.
Figure 2:
High-voltage and high-
current outputs on left-
hand side of
CPC 100
Caution
:
The connector "Ext. Booster" is
always
galvanically connected to
mains, regardless whether or not an external booster is selected on
the software tab
Options | Device Setup
, the green warning
warning light (0) is on, the outputs are turned off or the Emergency
Stop button is pressed.
Handle with extreme caution!
800A AC
(6.1-6.5V AC)
High AC current
output
POWER ON /OFF
switch
Mains power supply,
1 phase, 85V-264V AC
2kV AC
High-voltage
output
400A DC
(4-4.5V DC)
High DC current output
Ext. Booster
for example, for
the connection of
the
CP CB2
current booster
option for output
currents of up to
2000A
Grounding
terminal
Automatic circuit
breaker I > 16A
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...