Introduction
2 - 47
Principle Steps to Carry Out a Test with
CPC 100
1. Verify that the substation is prepared accordingly and you comply with all
safety regulations.
2.
Connect the
CPC 100
grounding terminal to the substation ground. Use
a wire with a cross-section of
≥
6mm², otherwise the housing may feed
high voltage.
3. Connect
CPC 100
to the mains power supply using the provided cable.
4.
With the test object grounded and shorted out
, connect
CPC 100
to the
test object according to your requirements.
5. Remove the grounding set from the test object.
6. Turn on
CPC 100
at its POWER switch at the left-hand side.
The green warning light "O" lights up, showing that none of
CPC 100
outputs
carries a dangerous voltage or current yet.
7. Set up your test in the
CPC 100
software, and, where applicable, determine
whether you want to perform an automatic or a manual test.
The following chapters of this manual comprise an example for each
available test.
For a detailed description of how to use the software refer to section ”How to
Use the CPC 100 Software” on page 17 of this chapter.
8. Once all test cards are prepared and the parameters set, make sure the
safety key lock is in position "release" (horizontal).
Connect
CPC 100
grounding terminal to
substation ground.
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...