Current Transformer
4 - 43
CT Low Power (Ratio)
Use the
CTLowPower
test card to measure the ratio of a low power current
transformer.
A low power current transformer contains a built-in burden, and provides an
output voltage that is directly proportional to the primary current. For both
protection and measurement only one transformer is required. A low power
current transformer provides a wide nominal current range, and operates linear
and without saturation through the entire range up to the short-circuit current.
To carry out this test, disconnect the ODU plug of the current transformer’s
secondary side from the protection relay, plug it into
CPC 100
V2AC
input, and
inject current up to 800 A from
CPC 100
800A AC
output or up to 2000 A using
the
CP CB2
current booster connected to the "
EXT. BOOSTER
" output to the
current transformer’s primary side.
Figure 24:
Setup for a CT ratio low
power test
Please refer to the note below.
electronic
protection
relay with
low
voltage
input (e.g.
22.5mV at
Inom)
built-in burden
shielded cable with
twisted wires
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...