Transformer
6 - 19
Figure 11:
Simplified schematic of
a tap changer
It is recommended to perform all winding resistance measurements with the
CP SA1
connected to the
CPC 100
V DC
input sockets to protect yourself and
CPC 100
from high-voltage hazards. The
CP SA1
must be used for
measurements using
400A DC
output. Before using
CP SA1
, you can check its
functionality by following the test procedure in ”CP SA1” on page 17-14. If the
box is defective, contact OMICRON electronics sales office (for ordering
information, see ”Ordering Information for CP SA1” on page 17-14). Before
disconnecting the test leads, short-circuit the transformer’s terminals first and
then remove the wirings to
CPC 100
.
OLTC
taps