![Omicron CPC 100 Reference Manual Download Page 74](http://html2.mh-extra.com/html/omicron/cpc-100/cpc-100_reference-manual_3988877074.webp)
CPC 100 V1.41
2 - 46
Putting
CPC 100
into Operation
Safety Aspects
We strongly advise you to obey the following legal safety aspects:
– Tests with such high voltages and currents must only be carried out by
authorized and qualified personnel.
– Personnel receiving training, instructions, directions, or education on high-
voltage/current tests should remain under the constant supervision of an
experienced operator while working with the equipment. The instructions
have to be renewed at least once per year.
– The instructions must be available in written form and signed by each person
assigned to do high-voltage/current tests.
Preparations in Substation
Prior to connecting a test object to
CPC 100
, the following steps need to be
carried out by an authorized employee of the utility.
– Turn off and disconnect the high voltage from the test object.
– Protect yourself and your working environment against an accidental re-
connection of high voltage by other persons and circumstances.
– Verify a safe isolation of the test object.
– Earth-connect and shorten out the test object’s terminals using a grounding
set.
– Protect yourself and your working environment with a suitable protection
against other (possibly live) circuits.
– Protect others from accessing the dangerous area and accidentally touching
live parts by setting up a suitable barrier and, if applicable, warning lights.
– If there is a longer distance between the location of
CPC 100
and the area of
danger (that is, the test object), a second person with an additional
"Emergency Stop" button is required.
Note:
Before setting
CPC 100
into operation and carrying out a test, it is
essential that you have read and understood the section ”Safety
Instructions for CPC 100 and its Accessories” on page 1-5.
Always be aware that all AC and DC output sockets of
CPC 100
can
carry life-hazardous voltage potential and provide life-hazardous
currents.
Summary of Contents for CPC 100
Page 12: ...CPC 100 V1 41 x...
Page 28: ...CPC 100 V1 41 1 16...
Page 90: ...CPC 100 V1 41 3 14...
Page 194: ...CPC 100 V1 41 6 30...
Page 250: ...CPC 100 V1 41 8 32 Figure 24 Settings of Amplifier test card for this example use case...
Page 258: ...CPC 100 V1 41 9 4...
Page 264: ...CPC 100 V1 41 10 6...
Page 282: ...CPC 100 V1 41 12 10 Figure 9 Saving tests with the CPC Editor...
Page 284: ...CPC 100 V1 41 12 12...
Page 312: ...CPC 100 V1 41 14 12...
Page 316: ...CPC 100 V1 41 15 4...
Page 350: ...CPC 100 V1 41 16 34...
Page 372: ...OMICRON Contact Addresses 22...