Image 7.26: “Advanced analysis of the speed controller” screen
No.
Action
1
The speed and time settings are generated automatically from the motor
data.
2
ISDSH and ENPO (hardware enable) must be set to "High".
3
Click "Start test signal" button
4
Observe the safety notice: When you confirm the safety notice a step
response is executed.
5
The oscilloscope is set automatically.
6
The faster the actual value approaches the setpoint, the more
dynamically the controller is set. The overshoot of the actual value should
not be more than 5-10 % of the setpoint (general figure) during the
settling process.
Table 7.18: Instructions for optimization of the speed controller
MOOG
ID No.: CB40859-001 Date: 11/2020
MSD Servo Drive - Device Help
138
7 Control
Image 7.27: Step response to rated speed
Creating the transfer function
The oscilloscope automatically records the amount and phase response of the
controller according to the controller settings. This produces an initial estimate of the
control quality.
To determine the transfer function the noise amplitude (motor rated current) and the
sampling time (default 0.125 ms) must be specified. Click the "Start Test Signal"
button.