User manual of EL8-EC***F AC Servo
94
Pr2.55
Label
Overshoot
suppression
gain
Mode
F
Range
0~1000
Unit
-
Default
0
Index
2255h
Activation
Immediate
Suppression improves with larger set value but might affect the performance of MFC. Please use
with caution for any value above 100.
3.2.4
【
Class 3
】
Velocity Control
Pr3.12
Label
Acceleration time settings
Mode
PV
CS
V
Range
0~10000
Unit
ms/
(1000RPM)
Default
0
Index
2312h
Activation
Immediate
Pr3.13
Label
Deceleration time settings
Mode
PV
CS
V
Range
0~10000
Unit
ms/
(1000RPM)
Default
0
Index
2313h
Activation
Immediate
Set max acceleration/deceleration for velocity command.
If target velocity =
x
[rpm], max acceleration =
a
[unit: rpm/ms], acceleration time =
t
[ms]
Pr3.12 =
1000
/
a
Pr3.13 =
1000
/
a
a = x/t
For example: If motor is to achieve 1500rpm in 30s,
a=1500/30=50rpm/ms
Pr3.12 = 1000/
a= 20.
Hence when Pr3.12 = 20, motor can achieve 1500rpm in 30s.
Velocity
(rpm)
Initial acceleration
time
With added
acceleration
deceleration
time settings
Time(ms)
1000
(rpm)
PA3.12
PA3.13
Usually used when there is rapid acceleration or trapezoidal wave velocity command due to many different internal
speed segments under velocity control mode which causes instable while motor in motion.
Under velocity control mode, 6083 and 6084 is limited by Pr3.12 and Pr3.13 correspondingly.