User manual of EL8-EC***F AC Servo
199
gone with the
first Z-signal
.
Z-signal
High velocity
6099h-01h
Start
Stop
-1
Limit switch Z-signal mode
Mode 1:
Diagram A:
Negative limit switch = OFF
1. Move in
negative direction
at
high velocity
until
negative limit switch valid.
2. Move in
positive direction
at
low velocity
and stops
after negative limit switch
and
first encoder Z-signal valid
Diagram B:
Negative limit switch = ON
1. Start to move at
negative limit switch position
in
positive
direction
at
high velocity
until
negative limit switch invalid.
2. Move in
negative direction
at
high velocity
until
negative limit switch valid.
3. Move in
positive direction
at
low velocity
and stops
after negative limit switch
and
first encoder Z-signal valid
If the positive limit signal is valid during the homing process, the status word (6041h) bit 13
will be valid, indicating homing error and the motor will stop immediately.
1
1
Z-signal
Negative limit
NOT
A:
NOT = OFF
B:
NOT = ON
Start
Stop
High velocity
6099h-01h
Low velocity
6099h-02h