54
2.16.6 Digital Input Signal Settings
When limit switch or emergency stop is used, POT, NOT and E-STOP signal will be
normally close (NC) by default. Please make sure there is no safety concern if these
signals need to be set to normally open (NO).
Servo drive power on signal (SRV-ON) is set as normally open (NO) as default.
Please make sure there is no safety concern if this signal needs to be set to normally
close (NC).
If a same function is assigned to multiple pins, Er210 might occur.
2.16.7 Digital Output Signal Settings
CN1
Signal
Parameter
Function
1
DO1+
Pr4.10
External break released
BRK-OFF
2
DO1-
25
DO2+
Pr4.11
Servo Ready
S-RDY
26
DO2-
3
DO3+
Pr4.12
Servo Alarm
(
ALARM
)
4
DO3-
Digital output functions can be assigned to multiple pins at the same time.
CN1 PIN
Signal
Parameter
Default function
Default status
6
DI-COM
-
Common DI
-
5
DI1
Pr4.00
-
Normally open
7
DI2
Pr4.01
POT
Normally open
8
DI3
Pr4.02
NOT
Normally open
9
DI4
Pr4.03
HOME-SWITCH
Normally open
10
DI5
Pr4.04
-
Normally open
11
DI6
Pr4.05
-
Normally open
12
DI7
Pr4.06
-
Normally open
13
DI8
Pr4.07
-
Normally open