HTX30 Product Manual
Appendix
8-45
Voltage demand group
Short name: VoDmd
Name
SCP text
Description
Min
Max
Default Units
Access
Voltage idle level
VIdle
The voltage demand for idle RPM.
0
120
0
V/10
C
Voltage full level
VFull
The voltage to demand for maximum RPM.
0
120
0
V/10
C
Ratiometric
reference
VRRef
Set when calibrating a ratiometric style voltage demand.
Compensates for changes in the external reference
voltage by scaling the demand voltage ratiometrically.
Set to zero to disable.
0
1023
0
F
Frequency demand group
Short name: FmDmd
Name
SCP text
Description
Min
Max
Default
Units
Access
Idle frequency
IdleF
The frequency of the output for idle RPM.
5
200
80
Hz
C
Full frequency
FullF
The frequency of the output for maximum RPM.
25
1000
480
Hz
C
PWM demand group
Short name: PwmDm
Name
SCP text
Description
Min
Max
Default Units
Access
Frequency
PwmHz
The basic frequency of the PWM demand.
200
2000
1000
Hz
C
Idle duty ratio
PwIdl
The duty ratio to demand for idle RPM.
0
45
5
%
C
Full duty ratio
PwFul
The duty ratio to demand for maximum RPM.
55
100
95
%
C
Low level voltage
PwLow
The voltage to output for a PWM low signal. For
example, if the PWM duty is 5% and this parameter is
5V, then the demand will spend 95% of the time at 5V.
0
120
0
V/10
C
High level voltage
PwmHi
The voltage to output for a PWM high signal. See Low
level voltage.
0
120
0
V/10
C
Actuator group
Short name: Actur
Name
SCP text
Description
Min
Max
Default Units
Access
Full
Full
2100
3845
3100
U
Idle
Idle
250
1300
500
U
Deadband
Dband
0
65535
200
D
Kp
Kp
0
1000
250
F
Ki
Ki
0
1000
0
F
Kd
Kd
0
1000
100
F
Close
Close
0
100
30
F
Maximum drive
MxDrv
0
100
100
F
Nudge
Nudge
0
100
40
F
Advanced group
Short name: Advcd
Name
SCP text
Description
Min
Max
Default Units
Access
Voltage output
alternate level
VAlt
The level to set the voltage demand to when it is
otherwised unused such as when the system is in
current or PWM demand modes. May be used as a
supply or reference to support circuitry.
0
120
0
V/10
D
Invert RPM
demand
InvtD
Set to invert the sense of the RPM demand. If set, then
the configured idle level is used for maximum RPM and
the configured maximum level is used for idle. For
example, in voltage mode with a configured idle level of
2.0V and a maximum level of 5.0V, then the EIM will
output 5.0V at idle and 2.0V at maximum.
0
1
0
D
Check that RPM
follows up
RPMFo
Set to check that the engine RPM follows the RPM
demand. Clear if the engine is not linear enough to
satisfy the RPM follow up check and often triggers the
alarm.
0
1
1
D