2.1 <KRP4A51 / KRP4A52 / KRP4A53 / KRP4A54> Wiring Adaptor for Electrical Appendices (2)
329
Adaptor
2.1.4 Electric Wiring Work and Initial Setting
1. Wiring
2. Depending on whether [voltage input] or [non voltage input], connect the wiring as shown below.
Input with Voltage.
Set the Voltage/Non voltage changeover switch (SS1) to VOLT.
Input with No Voltage.
Set the Voltage/Non voltage changeover switch (SS1) to NON VOLT.
3. Display signal retrieval (Output)
The normal operation output terminals (W1, W2) and error output terminals (W3, W4) are non-voltage output contacts.
(Permissive current is 10mA~3A per contact.)
Output is as given below.
Output
Both Ry1 and Ry2 is OFF.
Only Ry1 is ON.
Only Ry2 is ON.
System
Group control
OFF
All normal operation
At least one unit is stopped due to error or transmission error
between the adaptor and the indoor unit.
Normal operation
output (Ry1) ON
during normal
operation
Error Output (Ry2)
"ON" when the operation
is stopped by
malfunction, or when
there is a transmission
error between the adaptor
and the indoor unit.
DC24V
AC24V
AC100V
AC200V
Cautions: If using 100VAC or
200~240VAC, the power wiring
should be separated from the
input wiring.
Operation
status
Power
supply
Error status
KRP4A51
PC board of adaptor
Central monitoring panel
R
y1
R
y2
W
1
W
2
W
3
W
4
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...