40
6.1 Definition
Fundamental of DIII-NET
6. Group and Zone
6.1
Definition
Group control
The group means the indoor units connected by the same control wiring for remote controller (connected to terminal
P1 and P2) and all the unit in group have “the same setting” and “the same operation”.
The indoor units in the group are controlled by the remote controller for indoor unit.
The number of indoor units in one group is up to 16 units.
Zone control
The zone means the indoor units connected by the same control wiring for central remote controller (connected to
terminal F1 and F2) and all the unit in zone have “the same setting”.
The zone control of the indoor unit is operated by the central remote controller.
From 1 up to 64 zones can be controlled by the central remote controller.
The number of groups you can set in one zone is from 1 up to 64 groups.
Up to 16 units can be set in one group, and up to 64 groups (up to 128 units) can be connected.
6.2
Patterns of Group and Zone
Centralized controllers are capable of controlling/monitoring up to 64 groups of indoor units (hereafter “groups”).
The main functions of the centralized controllers include :
1. Collective starting/stopping of operation of the indoor units connected to the centralized controller.
2. Starting/stopping of operation, temperature setting, switching between temperature control modes and
enabling/disabling of operation with the hand-held remote control by zone or group .
3. Scheduling by zone or group .
4. Monitoring of the operation status by zone or group .
5. Display of the air conditioner operation history.
6. Compulsory contact stop input from the central monitoring panel (non-voltage, normally-open contact).
∗
A group of indoor units include:
∗
Zone control with the
centralized controller
∗
Zone control, which allows collective settings for more than one group, is available with the
centralized
controller
, which facilitates the setting operations.
1 One indoor unit without a remote control.
3 Up to 16 indoor units controlled with one or two remote controls.
One setting makes the same setting for all of the units in one zone.
Up to 128 zones can be set with one
centralized controller
.
(The maximum number of groups in one zone is 64.)
Groups can be zoned at will with the
centralized controller
.
Indoor units in one group can be divided into more than one zone.
1 Zone is not limited to 1 Group and vice versa.
2 One indoor unit controlled with one or two remote controls.
Zone 1
Up to 16 units
Two remote controls
No remote control
Remote control
Remote control
or
Indoor unit
Zone 5
Zone 2
Zone 3
Zone 4
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...