8.3 Combination of DCS302CA61·DCS301BA61·DST301BA61
Fundamental of DIII-NET
8.3
Combination of DCS302CA61·DCS301BA61·DST301BA61
Note:
The case of respective maximum connections is when 1 zone has 1 unit and 2 centralized controls are made.
System
Configuration
Centralized control equipment connection pattern
Central remote controller
DCS302CA61
Unified ON/OFF controller
DCS301BA61
Schedule timer
DST301BA61
1 through 4 units
—
—
1 through 16 units
—
1 unit
—
1 unit
1. Central remote controller
Up to 64 zones can be controlled and start/stop operation
for each group can be easily done.
2. intelligent Touch Controller
Up to 64 zones can be controlled and start/stop operation
for each group can be easily done.
3. intelligent Touch Cont Central remote
controller
By using any of the controllers, up to 64 zones can be
controlled and start/stop operation for each group can be
easily done.
4. Central remote cont Unified ON/OFF controller
By using the ON/OFF controller, up to 64 zones can be
controlled and start/stop operation for each group can be
done.
5. Central remote cont Schedule timer
Up to 64 zones can be controlled and a scheduled
operation for each zone can be done. In the weekly
schedule, the Start/Stop operation can be set twice a
day, and nonworking days can be set according to the
day of a week.
6. Unified ON/OFF cont Schedule timer
Start/stop operation for up to 64 groups can be
individually set, start/stop operation can be set twice a
day on the weekly schedule, and nonworking days can
be set according to the day of a week. Scheduled
collective start/stop operation can be set.
Central remote controller
intelligent Touch Controller
Central remote
controller
intelligent
Touch Controller
Central remote
controller
Unified
ON/OFF controller
Central remote
controller
Schedule
timer
Unified ON/OFF
controller
Schedule
timer
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...