2.1 <KRP4A51 / KRP4A52 / KRP4A53 / KRP4A54> Wiring Adaptor for Electrical Appendices (2)
325
Adaptor
2. Adaptor for Indoor Unit and Other Equipment
2.1
<KRP4A51 / KRP4A52 / KRP4A53 / KRP4A54> Wiring Adaptor for Electrical
Appendices (2)
2.1.1 Function
This adaptor is an interface required to connect the indoor unit with the BAS.
And by installing this adaptor in the indoor unit, it enables you to have various
remote controls (ON/OFF, temperature setting, operation status display and
malfunction display). One adaptor can control simultaneously the group of
units (Max. 16 units) connected to the remote control wiring line (P1, P2).
Note:
1. This adaptor cannot be used together with central control equipment and data station.
2. The model of adaptor differs according to the type of indoor unit to be installed.
Type
BRC1C62
KRP4A51/52/53/54
Group/Zone
Item
One Group
One Group
ON/OFF
Possible
Possible
Temp. setting
Possible
Possible
Air flow rate setting
Possible
Impossible
Air flow direction setting
Possible
Impossible
Timer setting twice a day
Possible
Impossible
Mode setting
Possible
Impossible
Filter sign reset
Possible
Impossible
Inspection/Test operation
Possible
Operation & Error
display only by lamps
Note:
1. Marked
shows wiring adaptor for electrical appendices.
2. Marked
indicates the same control range.
3. The wiring adaptor for electrical appendices (2) can control simultaneously the group of the units (Max. 16 units)
connected to the remote control wiring line (P1, P2). In another words, all the units connected between P1 and P2
terminal have the same control.
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...