178
2.1 System Configuration of intelligent Manager
intelligent Manager
2. System Design of intelligent Manager
2.1
System Configuration of intelligent Manager
2.2
List of Required Devices for intelligent Manager System
Device
Classification
Prepared by
Model / Spec.
Remarks
iPU
Essential
Daikin
DAM602B51
Model with a 4-port D3 port
DAM602B52
Model with a 2-port D3 port
PC
Essential
Customer
Pentium III 800MHz or faster
Memory 256MB or more
HD 4GB or more
PC for intelligent Manager
Windows XP Professional SP2 or later
Windows 2000 Professional SP4 or later
Up to 2 units can be installed on LAN.
Monitor
Essential
Customer
Resolution of 800 x 600 or higher
800×600 or 1,024×768 or 1,280×1,024
HUB
Essential
Customer
100 Base/T
Used to connect iPU and PC.
UPS
Essential
Customer
APC SU700 or SU1000 series
Supplies power to iPU, PC and HUB.
Essential
Customer
APC AP9610
Required to transmit a power failure signal of UPS to
iPU.
Di/Dio
Op
Daikin
DEC101A51 (Di)
DEC102A51 (Dio)
Used to connect devices of other companies.
Ai
Op
Daikin
DAM101A51
Used to measure outside air temperature.
Modem
Op
Customer
Specified by service division
Required for Airnet connection.
One unit is required for each intelligent Manager
system.
kWh
meter
Op
Customer
Pulse output: 1kWh/pulse
Pulse width: 40 - 400 msec
Required when PPD is used.
The number of units will be determined in
accordance with the design.
PLC
Op
Customer
OMRON SYSMAC CJ1
Used to measure analog values such as
temperature, humidity, and pressure.
Op
Customer
CJ1W-PTS
Temperature measurement terminal
Op
Customer
CJ1W-AD etc. ...
Analog value measurement terminal
Pulse signal
I/O
DIII net
LAN (Ethernet)
HUB
UPS
Power Line
PC
iPU
Fire detection System, etc.
RS232C
Contact signal
Contact signal
DIII
Device
DeviceNet
When using measurement
function of PLC
Optional function
Modem
When using
Air Conditioning
Network Service System
Optional function
*UP to 4 units of iPU can be connected
kWh meter
(1kWh/pulse)
Optional function
When using
proportional power
ACC center
Standard configuration
System Configuration Diagram
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...