8.3 Combination of DCS302CA61·DCS301BA61·DST301BA61
53
Fundamental of DIII-NET
7. Central remote cont Unified ON/OFF controller
+ Schedule timer
Up to 64 groups can be controlled and a scheduled
operation for each zone can be done.
Start/stop operation can be set twice a day on the weekly
schedule, and nonworking days can be set according to
the day of a week. Start/stop operation for each group
can be done by the ON/OFF controller.
8. intelligent Manager III + Unified ON/OFF controller
Up to 8 units can be installed on one DIII-NET.
(4 units with a main setting, and other 4 units with a sub-
setting)
9. Central remote controller × 4
10.Forced shutdown from external equipment
The central remote controller and ON/OFF controller are
equipped with a forced shutdown input terminal. If a
shutdown signal for air-conditioning machines is entered,
the machines are shut down collectively.
Note)
1. Do not use the forced shutdown input terminal when a
data station is used simultaneously.
2. The unified ON/OFF controller and schedule timer
also can be used individually.
Central
remote controller
Unified ON/OFF
controller
Schedule
timer
intelligent Manager
Unified ON/OFF controller
Main (Master)
Sub (slave)
Central remote
controller
Unified ON/OFF controller
Forced stop signal,
No voltage, Constant "a" contact
Wiring length: no more than 150 m
If input is made to any controller,
all indoor units will stop.
During forced stop input, operation
cannot be made on the local side.
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...