2.5 <DTA103A51> Wiring Adaptor for Other Air Conditioners
347
Adaptor
<Setting Group No. for Centralized Control>
Set the group No. at the central control group No. setting switches (RS1 and RS2). Refer to the below table to set
group No. Group No. increases in the order of 1-00, 1-01 ... 1-15, 2-00, ... 4-15. Refer to the installation manual of the
optional controller.
RS1 Switch Setting and Upper Group No. Position
RS2 Switch Setting and Lower Group No. Position
Make Settings before Turning ON The Power.
Note:
Group number need not be set on this adaptor during individual use with either a wiring adaptor for electrical appendices
or a schedule timer. Setting is automatic.
Ex. Setting group No. 1-15
First and second group No.s are indicated as below.
<Power Supply Wiring>
Power supply can be selected from a 1
~
50 Hz 220-240V source and a 1
~
60 Hz 220V source. Check power supply
specifications and properly wire the source to the adaptor.
Note:
Ground wires as shown in the figure on the right.
The adaptor may malfunction or be damaged if improperly wired.
The fuse is designed for short-circuit protection (Overcurrent protection).
Therefore, it may not offer sufficient protection against improper voltage.
2PA53853
Position
0
1
2
3
4
5
6
7
8
9
Group No.
—
1
2
3
4
—
—
—
—
—
Position
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Group No.
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...