1.2 <KRP2A61 / KRP2A62 / KRP2A53> Wiring Adaptor for Electrical Appendices (1)
283
Adaptor
For demand control from input B
Forced thermostat OFF command
Forces indoor unit to operate the fan only.
Forced temperature shift command
The indoor unit operates at 2°C higher (cooling) or 2°C lower (heating) than the set temperature.
Note:
In zone control, operation is displayed as long as one indoor unit is running. When in the last command priority mode,
some units are not operating while ON.
In such case, even if input A is ON, the unit and all other units in the same zone will stop.
4 When operating with dual pulse inputs from A and B (Use a pulse input of 200 milli-sec. or longer.)
Note:
Doing constant input A with position 7-A, it will be forced OFF function (input A is ignored).
Constant input cannot use for input B with position B.
1PA63642B
Position
Function when input A is ON
Function when input B is ON
C
Remote controller rejected (Same as position”5”)
Forced thermostat OFF command
D
Forced temperature shift command
E
Last command priority (Same as position “6”)
Forced thermostat OFF command
F
Forced temperature shift command
Position
Function
Input A ON
Input B ON
Operation or
not of indoor
unit
From Remote controller
Operation or
not of indoor
unit
From Remote controller
7
Remote Control Rejection
ON
Rejection
OFF
Rejection
8
Central Priority
ON
Acceptable
9
Stop by Remote controller
Acceptable
ON
Only Stop acceptable
A
Remote controller acceptance /
rejection
Permit
Acceptable
B
Last command Priority
ON
Acceptable
OFF
Acceptable
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...