1.3 <DTA104A61 / DTA104A62 / DTA104A53> External Control Adaptor for Outdoor Unit (Must be Installed on Indoor Units)
Adaptor
Fig. 2
(Ex.) To set the outdoor unit’s cool/heat address to No. 15 :
—Off —On —Flicker
5-bit
Procedure
Setting contents
MODE
TEST
C/H SELECT
L.N.O.P.
SEQ.
START
IND
MASTER SLAVE
When power turned on
Setting mode (factory set)
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Hold down next page button for
5 sec.
Enters address setting.
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Push operation button one time.
Enters cool/heat address
setting.
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Push confirmation button one
time.
Make sure cool/heat address
has been entered.
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Push operation button 15 times.
(Address No. = Times pushed)
Sets cool/heat address.
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Push confirmation button two
times.
Check cool/heat address.
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Push next page button one time. Returns to set mode.
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Fig. 3 (Ex.) To set the outdoor unit’s demand address to No. 7 :
—Off —On —Flicker
5-bit
Procedure
Setting contents
MODE
TEST
C/H SELECT
L.N.O.P.
SEQ.
START
IND
MASTER SLAVE
When power turned on
Setting mode (factory set)
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Hold down next page button for
5 sec.
Enters address setting.
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Push operation button two times. Enters demand address setting.
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Push confirmation button one
time.
Make sure demand address has
been entered.
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Push operation button 7 times.
(Address No. = Times pushed)
Sets demand address.
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Push confirmation button two
times.
Check demand address.
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Push next page button one time. Returns to set mode.
LED20
LED21
LED22
LED23
LED24
LED25
LED25
Fig. 1
: OFF
: ON
C/H
LOWER
ADRESS
CENTRAL
NO.
DEMAND CONTROL ADRESS
Setting of 5-bit cool/heat
address by DS1,2
Designate and set cool/heat
addresses 0-31 for each
operation mode switch unit.
No. 0
No. 7
No. 8
No. 15
No. 16
No. 31
Upper 2
bits DS2
Lower 3
bits DS1
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...