1.9 Electric Wiring
209
Interface for Use in BACnet
®
2. No Voltage Contact Input Wiring
1P191170C
100~400ms
100ms Over
DMS502B51
Di
1
G
2
3
G
4
Di
Di
1
G
2
3
G
4
11
G
12
13
G
G
14
15
16
The pulse of watt hour meter
watt hour meter
watt hour meter
watt hour meter
watt hour meter
watt hour meter
watt hour meter
DIII-1
Force OFF input
DIII-2
Force OFF input
DIII-3
Force OFF input
DIII-4
Force OFF input
(Note): Use a meter that outputs one pulse of a width from 100~400ms, per one kWh.
Recommended wire size 0.75~1.25mm
2
Cautions for wiring
1. The input are all the no voltage contact
2. Use a contact which can guarantee minimum application load DC16V and 10mA
3. Do not use multicore cables with three or more cores
4. Use wires of sizes between 0.75mm
2
and 1.25mm
2
5. Do not bind the wire for control
6. Wirings for control must be isolated from the power lines
7. Terminals G are inter-connected. Connecting to either one is allowed, but the number of cables connectable
to one terminal is limited to 2 pieces
8. Wire length : Max 150m
Recommended wire size 0.75~1.25mm
2
* This connector cannot be used with this unit
(Note)
DAM412B51
Summary of Contents for D-BACS
Page 1: ...ED 72 721 Preliminary Daikin Buildings Air conditioning Control System D BACS DESIGN GUIDE ...
Page 17: ...xvi 1 5 Open Network Glossary Introduction ...
Page 41: ...24 Outline of D BACS System ...
Page 74: ...57 Remote Controllers HRV Wired remote controller BRC301B61 VAM ...
Page 107: ...90 5 4 HRV BRC301B61 Remote Controllers ...
Page 142: ...1 2 System Configuration 125 Control Devices 1 2 System Configuration System Outline ...
Page 181: ...164 3 8 Error Diagnosing Function Control Devices ...
Page 215: ...198 3 8 Wiring Example intelligent Manager ...
Page 235: ...218 Interface for Use in BACnet ...
Page 253: ...236 Interface for use in LONWORKS 10 Reference Materials Error Code Conversion Table ...
Page 268: ...251 Interface for use in LONWORKS 13 Workflow ...
Page 285: ...268 1 6 Notes Power Proportional Distribution P P D ...